Título
A PERFORMANCE ANALYSIS OF TRANSMISSION LINE DIFFERENTIAL PROTECTION

Publicado no livro
ENGENHARIAS - AUTOMAÇÃO, ROBÓTICA, METROLOGIA E ENERGIA: ESTUDOS E TENDÊNCIAS - VOLUME 3Capítulo
1
Páginas
11-25
Publicado em
01/09/2023
Autores
- Igor Ferreira PradoUESC
- Rodrigo Prado De MedeirosUFERSA
- Flávio Bezerra CostaUFRN
- Kleber Melo SilvaUnB
Resumo
This work accomplishes a comparative analysis between two transmission line differential protection methodologies available in commercial relays: percentage and alpha-plane differential protections. In order to verify the operation limits of the protections, several internal and external faults were simulated considering variations of the fault location, fault inception angle, fault impedance, and TC saturation. The alpha-plane method presented was the most accurate and fastest since the sequence units were not influenced by the fault impedance.
Palavras-chave
Transmission Line Protection, Percentage Differential Protection, Alpha-Plane Differential Protection.
Licença
Este capítulo está sob a Licença Creative Commons Atribuição-NãoComercial-SemDerivações 4.0 Internacional .

O conteúdo do capítulo, seus dados, forma, correção e confiabilidade são de responsabilidade exclusiva do(s) autor(es). É permitido o download e o compartilhamento, desde que pela origem e no formato Acesso Livre (Open Access), com os devidos créditos e a citação atribuídos ao(s) respectivo(s) autor(es). Não é permitida qualquer alteração, catalogação em plataformas de acesso restrito ou utilização para fins comerciais. O(s) autor(es) mantém os direitos autorais do texto.