A PERFORMANCE ANALYSIS OF TRANSMISSION LINE DIFFERENTIAL PROTECTION
Igor Ferreira Prado
Prado, Igor Ferreira
Rodrigo Prado De Medeiros
MEDEIROS, R. P.
Flávio Bezerra Costa
COSTA, F. B.
Kleber Melo Silva
SILVA, K. M.
01/09/2023
11-25
1
ENGENHARIAS - AUTOMAÇÃO, ROBÓTICA, METROLOGIA E ENERGIA: ESTUDOS E TENDÊNCIAS - VOLUME 3
This work accomplishes a comparative analysis between two transmission line differential protection methodologies available in commercial relays: percentage and alpha-plane differential protections. In order to verify the operation limits of the protections, several internal and external faults were simulated considering variations of the fault location, fault inception angle, fault impedance, and TC saturation. The alpha-plane method presented was the most accurate and fastest since the sequence units were not influenced by the fault impedance.
Transmission Line Protection, Percentage Differential Protection, Alpha-Plane Differential Protection.
Este capítulo está licenciado com uma Licença Creative Commons Atribuição-NãoComercial-SemDerivações 4.0 Internacional.
O conteúdo do capítulo e seus dados e sua forma, correção e confiabilidade, são de responsabilidade exclusiva do(s) autor(es). É permitido o download e compartilhamento desde que pela origem e no formato Acesso Livre (Open Access), com os créditos e citação atribuídos ao(s) respectivo(s) autor(es). Não é permitido: alteração de nenhuma forma, catalogação em plataformas de acesso restrito e utilização para fins comerciais. O(s) autor(es) mantêm os direitos autorais do texto.